# MAVLink Peripherals (GCS/OSD/Gimbal/Camera/Companion)
|
|
|
|
Ground Control Stations (GCS), On-Screen Displays (OSD), MAVLink Cameras & Gimbals, Remote IDs, Companion Computers, ADS-B receivers, and other MAVLink peripherals interact with PX4 using separate MAVLink streams, sent via different serial ports.
|
|
|
|
In order to configure that a particular serial port is used for MAVLink traffic with a particular peripheral, we use [Serial Port Configuration](../peripherals/serial_configuration.md), assigning one of the abstract "MAVLink instance" configuration parameters to the desired port.
|
|
We then set other properties of the MAVLink channel using the parameters associated with our selected MAVLink instance, so that they match the requirements of our particular peripheral.
|
|
|
|
The most relevant parameters are described below (the full set are listed in the [Parameter Reference > MAVLink](../advanced_config/parameter_reference.md#mavlink)).
|
|
|
|
## MAVLink 인스턴스
|
|
|
|
In order to assign a particular peripheral to a serial port we use the concept of a _MAVLink instance_.
|
|
|
|
Each MAVLink instance represents a particular MAVLink configuration that you can apply to a particular port.
|
|
At time of writing three MAVLink _instances_ are defined, each represented by a parameter [MAV_X_CONFIG](#MAV_X_CONFIG), where X is 0, 1, 2.
|
|
|
|
Each instance has associated parameters that you can use to define the properties of the instance on that port, such as the set of streamed messages (see [MAV_X_MODE](#MAV_X_MODE) below), data rate ([MAV_X_RATE](#MAV_X_RATE)), whether incoming traffic is forwarded to other MAVLink instances ([MAV_X_FORWARD](#MAV_X_FORWARD)), and so on.
|
|
|
|
:::info
|
|
MAVLink instances are an abstract concept for a particular MAVLink configuration.
|
|
The number in the name means nothing; you can assign any instance to any port.
|
|
:::
|
|
|
|
각 인스턴스의 매개변수는 아래와 같습니다.
|
|
|
|
- <a id="MAV_X_CONFIG"></a>[MAV_X_CONFIG](../advanced_config/parameter_reference.md#MAV_0_CONFIG) - Set the serial port (UART) for this instance "X", where X is 0, 1, 2.
|
|
It can be any unused port, e.g.: `TELEM2`, `TELEM3`, `GPS2` etc.
|
|
For more information see [Serial Port Configuration](../peripherals/serial_configuration.md).
|
|
- <a id="MAV_X_MODE"></a>[MAV_X_MODE](../advanced_config/parameter_reference.md#MAV_0_MODE) - Specify the [MAVLink profile](../mavlink/mavlink_profiles.md) for the instance, such as _Normal_ or _OSD_.
|
|
Profiles define a particular set of streamed messages and their rates — you should choose a profile that is appropriate for your channel and the peripheral.
|
|
- <a id="MAV_X_RATE"></a>[MAV_X_RATE](../advanced_config/parameter_reference.md#MAV_0_MODE) - Set the maximum _data rate_ for this instance (bytes/second).
|
|
- 이는 개별 메시지의 모든 스트림에 대한 결합 비율입니다 (총 비율이이 값을 초과하면 개별 메시지에 대한 비율이 감소됨).
|
|
- 기본 설정은 일반적으로 허용되지만 원격 분석 링크가 포화 상태가 되고, 너무 많은 메시지가 삭제되는 경우에는 감소할 수 있습니다.
|
|
- 값이 0이면 데이터 속도가 이론적인 값의 절반으로 설정됩니다.
|
|
- <a id="MAV_X_FORWARD"></a>[MAV_X_FORWARD](../advanced_config/parameter_reference.md#MAV_0_FORWARD) - Enable forwarding of MAVLink packets received by the current instance onto other interfaces.
|
|
예를 들어 GCS가 보조 컴퓨터에 연결된 MAVLink 지원 카메라와 통신할 수 있도록 GCS와 보조 컴퓨터간에 메시지를 전송에 사용할 수 있습니다.
|
|
|
|
Next you need to set the baud rate for the serial port you assigned above (in `MAV_X_CONFIG`).
|
|
|
|
:::tip
|
|
You will need to reboot PX4 to make the parameter available (i.e. in QGroundControl).
|
|
:::
|
|
|
|
The parameter used will depend on the [assigned serial port](../advanced_config/parameter_reference.md#serial) - for example: `SER_GPS1_BAUD`, `SER_TEL2_BAUD`, etc.
|
|
사용하는 값은 연결 유형과 연결된 MAVLink 주변 장치에 따라 달라집니다.
|
|
|
|
## Default MAVLink Ports {#default_ports}
|
|
|
|
### TELEM1
|
|
|
|
The `TELEM 1` port is almost always configured by default for the GCS telemetry stream ("Normal").
|
|
|
|
To support this there is a [default serial port mapping](../peripherals/serial_configuration.md#default_port_mapping) of MAVLink instance 0 as shown below:
|
|
|
|
- [MAV_0_CONFIG](../advanced_config/parameter_reference.md#MAV_0_CONFIG) = `TELEM 1`
|
|
- [MAV_0_MODE](../advanced_config/parameter_reference.md#MAV_0_MODE) = `Normal`
|
|
- [MAV_0_RATE](../advanced_config/parameter_reference.md#MAV_0_RATE)= `1200` Bytes/s
|
|
- [MAV_0_FORWARD](../advanced_config/parameter_reference.md#MAV_0_FORWARD) = `True`
|
|
- [SER_TEL1_BAUD](../advanced_config/parameter_reference.md#SER_TEL1_BAUD) = `57600`
|
|
|
|
### TELEM2
|
|
|
|
The `TELEM 2` port usually configured by default for a companion computer telemetry stream ("Onboard").
|
|
|
|
To support this there is a [default serial port mapping](../peripherals/serial_configuration.md#default_port_mapping) of MAVLink instance 0 as shown below:
|
|
|
|
- [MAV_1_CONFIG](../advanced_config/parameter_reference.md#MAV_0_CONFIG) = `TELEM 2`
|
|
- [MAV_1_MODE](../advanced_config/parameter_reference.md#MAV_0_MODE) = `Onboard`
|
|
- [MAV_1_RATE](../advanced_config/parameter_reference.md#MAV_0_RATE)= `0` (Half maximum)
|
|
- [MAV_1_FORWARD](../advanced_config/parameter_reference.md#MAV_0_FORWARD) = `Disabled`
|
|
- [SER_TEL2_BAUD](../advanced_config/parameter_reference.md#SER_TEL2_BAUD) = `921600`
|
|
|
|
### ETHERNET
|
|
|
|
Pixhawk 5x devices (and later) that have an Ethernet port, configure it by default to connect to a GCS:
|
|
|
|
On this hardware, there is a [default serial port mapping](../peripherals/serial_configuration.md#default_port_mapping) of MAVLink instance 2 as shown below:
|
|
|
|
- [MAV_2_CONFIG](../advanced_config/parameter_reference.md#MAV_2_CONFIG) = `Ethernet` (1000)
|
|
- [MAV_2_BROADCAST](../advanced_config/parameter_reference.md#MAV_2_BROADCAST) = `1`
|
|
- [MAV_2_MODE](../advanced_config/parameter_reference.md#MAV_2_MODE) = `0` (normal/GCS)
|
|
- [MAV_2_RADIO_CTL](../advanced_config/parameter_reference.md#MAV_2_RADIO_CTL) = `0`
|
|
- [MAV_2_RATE](../advanced_config/parameter_reference.md#MAV_2_RATE) = `100000`
|
|
- [MAV_2_REMOTE_PRT](../advanced_config/parameter_reference.md#MAV_2_REMOTE_PRT)= `14550` (GCS)
|
|
- [MAV_2_UDP_PRT](../advanced_config/parameter_reference.md#MAV_2_UDP_PRT) = `14550` (GCS)
|
|
|
|
For more information see: [PX4 Ethernet Setup](../advanced_config/ethernet_setup.md)
|
|
|
|
## Device Specific Setup
|
|
|
|
Links to setup instructions for specific MAVLink components:
|
|
|
|
- [MAVLink Cameras (Camera Protocol v2) > PX4 Configuration](../camera/mavlink_v2_camera.md#px4-configuration)
|
|
- [Gimbal Configuration > MAVLink Gimbal (MNT_MODE_OUT=MAVLINK)](../advanced/gimbal_control.md#mavlink-gimbal-mnt-mode-out-mavlink)
|
|
|
|
## See Also
|
|
|
|
- [MAVLink Profiles](../mavlink/mavlink_profiles.md)
|
|
- [Serial Port Configuration](../peripherals/serial_configuration.md)
|
|
- [PX4 Ethernet Setup > PX4 MAVLink Serial Port Configuration](../advanced_config/ethernet_setup.md#px4-mavlink-serial-port-configuration)
|
|
- [Serial Port Mapping](../hardware/serial_port_mapping.md)
|